Marel Electric
WTK thermocouple amplifiers

Temperature sensor amplifier

WTK-100

The WTK-100 converts the low-voltage thermocouple signal into a standard 4–20 mA current signal. The compact housing with a polyamide terminal block allows mounting on a TS-32 or TS-35 rail. A built-in sensor compensates for ambient temperature fluctuations, and connections should be made with shielded cable of at least 2 × 0.2 mm²

Every amplifier in the WTK series works with a type K or J thermocouple and is compatible with the Autronica Sunderland Forge temperature transmitter. The model is equivalent to GA-100

Thermocouple amplifier WTK-100

Technical specification

Supply voltage
24 VDC (16–36 VDC)
Output signal
4–20 mA
Signal on sensor failure
3,5–4 mA
Maximum current draw
30 mA
Load resistance
0–1130 Ω
Operating temperature
-25 °C do +75 °C
Temperature compensation range
0 °C do +70 °C
Accuracy
< ±1,0 % zakresu sygnału wyjściowego
Repeatability
< ±0,2 % zakresu sygnału wyjściowego
Zero and gain drift
< 0,05 °C/°C zmiany temperatury otoczenia
Dimensions (H × W × D)
28 × 40 × 40 mm
Weight
61,5 g
Housing material
poliamidowy blok zaciskowy
Mounting
szyna TS-32 lub TS-35
Ingress protection
IP64

Available versions

Model WTK-100 is manufactured in versions for different temperature ranges and thermocouple types

AutronicaMarelRangeSensor type
GA-100 /EWTK-100 /E0 °C do 160 °CK NiCr-NiAl
GA-100 /BWTK-100 /B0 °C do 300 °CK NiCr-NiAl
GA-100 /AWTK-100 /A0 °C do 600 °CK NiCr-NiAl
GA-100 /NWTK-100 /N0 °C do 900 °CK NiCr-NiAl
GA-100 /GWTK-100 /G0 °C do 300 °CJ Fe-Constantan
GA-100 /FWTK-100 /F0 °C do 600 °CJ Fe-Constantan

Ask about WTK-100

We sell, select and service WTK amplifiers. We are happy to help choose the right version for your measurement setup