Marel Electric
WTK thermocouple amplifiers

Temperature sensor amplifier

WTK-2

The WTK-2 converts the low-voltage thermocouple signal into a 2.4–8.25 mA current signal, replicating the characteristic of the original modules used in older monitoring systems. The compact housing with screw terminals allows mounting on a TS-32 or TS-35 rail

Every amplifier in the WTK series works with a type K or J thermocouple and is compatible with the Autronica Sunderland Forge temperature transmitter. The model is equivalent to GA-2

Thermocouple amplifier WTK-2

Technical specification

Supply voltage
24 VDC (16–36 VDC)
Output signal
2,4–8,25 mA
Signal on sensor failure
2,5–3 mA
Maximum current draw
20 mA
Load resistance
0–3340 Ω
Operating temperature
-25 °C do +75 °C
Temperature compensation range
0 °C do +75 °C
Accuracy
< ±1,0 % zakresu sygnału wyjściowego
Repeatability
< ±0,2 % zakresu sygnału wyjściowego
Dimensions (H × W × D)
28 × 40 × 40 mm
Weight
61,5 g
Ingress protection
IP64

Available versions

Model WTK-2 is manufactured in versions for different temperature ranges and thermocouple types

AutronicaMarelRangeSensor type
GA-2 /EWTK-2 /E0 °C do 160 °CK NiCr-NiAl
GA-2 /BWTK-2 /B0 °C do 300 °CK NiCr-NiAl
GA-2 /AWTK-2 /A0 °C do 600 °CK NiCr-NiAl
GA-2 /NWTK-2 /N0 °C do 900 °CK NiCr-NiAl
GA-2 /GWTK-2 /G0 °C do 300 °CJ Fe-Constantan
GA-2 /FWTK-2 /F0 °C do 600 °CJ Fe-Constantan

Ask about WTK-2

We sell, select and service WTK amplifiers. We are happy to help choose the right version for your measurement setup