General Details
The WTK-5 device converts the low voltage output from a thermocouple to a standard 1 – 5 mA signal. The power supply should be 15 VDC. The thermocouple is connected to the input of the amplifier. The input voltage is dependent upon the temperature difference between the sensor and the amplifier. Fluctuations in temperature are compensated by the built-in temperature sensor. A screened cable should always be used from the sensor to the amplifier and from the amplifier to the monitoring system. Minimum cross section cable is 2 x 0.2 mm2. Amplifier can be mounted with two screws.

Autronica MAREL equivalent: Range Sensor tpye
GA-5 /E WTK-5 /E 0°C to 160°C K NiCr-NiAl
GA-5 /B WTK-5 /B 0°C to 300°C K NiCr-NiAl
GA-5 /A WTK-5 /A 0°C to 600°C K NiCr-NiAl
GA-5 /N WTK-5 /N 0°C to 900°C K NiCr-NiAl
GA-5 /G WTK-5 /G 0°C to 300°C J Fe-Constantan
GA-5 /F WTK-5 /F 0°C to 600°C J Fe-Constantan
Technical Details
  • Power supply: 15 VDC
  • Output signal: 1 – 5 mA
  • Iout at broken sensor leader: 0.5 to 1 mA
  • Maximum current consumption: 10 mA
  • Load resistance: 0 to 1220 Ω
  • Ambient temperature, operation: -25 to +75 °C
  • Compensated temperature range: 0 to +70 °C
  • Accuracy: < ±1.0 % of FRO* (incl. non linearity, hysteresis and repeatability at 22 °C)
  • Repeatability: < ±0.2 % of FRO*
  • Thermal zero and sensitivity shift: < 0.05 °C/°C ambient temperature shift
  • Dimensions (H x W x D): 44 x 50 x 50 mm
  • Weight: 67.5 g
  • Housing material: Polyamide terminal block
  • Mounting: two screws
  • Encapsulation: IP64
Ask about this product

Contact form

  • 2 + 28 =
Documents